2001 Metals Scan

We do some routine metal scans, just to keep track of what might be influencing our water.

The analysis of these tests was done by Environmental Laboratories, Inc., in Madison, Indiana.



BDL = Below Detection Level

2001 Metals Testing, EP#1
Element tested for
Date Sampled
Detection Limit
Result
Maximum Contaminant Level
Metals
Antimony
04/02/2001
.003 mg/l
<.003 mg/l
.006 mg/l
Arsenic
04/02/2001
.001 mg/l
<.001 mg/l
.050 mg/l
Barium
04/02/2001
.010 mg/l
.002 mg/l
2.000 mg/l
Beryllium
04/02/2001
.0002 mg/l
<.0002 mg/l
.004 mg/l
Cadmium
04/02/2001
.0001 mg/l
<.0001 mg/l
.005 mg/l
Chromium
04/02/2001
.002 mg/l
<.002 mg/l
.100 mg/l
Cyanide, Total
04/02/2001
.005 mg/l
<.005 mg/l
.200 mg/l
Mercury
04/02/2001
.0001 mg/l
<.0001 mg/l
.002 mg/l
Nickel
04/02/2001
.0010 mg/l
<.0010 mg/l
.100 mg/l
Selenium
04/02/2001
.0020 mg/l
<.0020 mg/l
.050 mg/l
Sodium
04/02/2001
.1000 mg/l
27.5 mg/l
not regulated
Thallium
04/02/2001
.0020 mg/l
<.0020 mg/l
.0020 mg/l